5. Limitations: what fails and by how much

Every number below links to its source. Where I state an interpretation rather than a reported fact, it says so.

5.1 Sim-to-real: 1.3 % on hardware against 0.4 % in simulation

Evidence Simulation Hardware Ratio Source
LUMEN 4-valve SAC, mean tracking error 0.4 % nominal, 0.5 % domain-randomised 1.3 % (run 2) ≈ 3× thesis Table 6.2
Same, mixture ratio only 0.3 % / 0.5 % 2.7 % (max 8.5 %) 5–9× same
Same, first attempt — 7.8 % mean, 64.7 % max, "unstable" — same; p. 149
Cold-gas chamber pressure SAC, trajectory RMSE 0.36 bar 1.15 bar 3.2× Hörger et al. 2024, p. 9
22 N thruster, \(p_{cc}\) and \(R_{OF}\) controller — "Control performance in simulation is better than at the real system" — Hörger et al. 2025 (abstract)
{
  "$schema": "https://vega.github.io/schema/vega-lite/v6.json",
  "title": {"text": "How much worse on hardware than in simulation", "subtitle": "Hardware error ÷ simulation error (my derivation from thesis Table 6.2 and Hörger et al. 2024, p. 9)"},
  "width": "container", "height": 200,
  "layer": [
    {"data": {"values": [
        {"item": "LUMEN · chamber pressure", "ratio": 1.2, "calc": "0.7 % / 0.6 %"},
        {"item": "LUMEN · coolant flow", "ratio": 2.2, "calc": "1.1 % / 0.5 %"},
        {"item": "LUMEN · mean of four outputs", "ratio": 2.6, "calc": "1.3 % / 0.5 %"},
        {"item": "LUMEN · injection temperature", "ratio": 2.7, "calc": "0.8 % / 0.3 %"},
        {"item": "Cold-gas rig · trajectory RMSE", "ratio": 3.2, "calc": "1.15 bar / 0.36 bar"},
        {"item": "LUMEN · mixture ratio", "ratio": 5.4, "calc": "2.7 % / 0.5 %"}]},
     "layer": [
       {"mark": {"type": "bar", "cornerRadiusEnd": 4, "height": 16, "color": "var(--viz-s1)"},
        "encoding": {"y": {"field": "item", "type": "nominal", "sort": null, "title": null, "axis": {"labelLimit": 260}},
          "x": {"field": "ratio", "type": "quantitative", "title": "Hardware ÷ simulation", "scale": {"domain": [0, 6]}},
          "tooltip": [{"field": "item"}, {"field": "calc", "title": "hardware / simulation"}, {"field": "ratio", "title": "ratio"}]}},
       {"mark": {"type": "text", "align": "left", "dx": 5},
        "encoding": {"y": {"field": "item", "type": "nominal", "sort": null}, "x": {"field": "ratio", "type": "quantitative"}, "text": {"field": "ratio", "format": ".1f"}}}
     ]},
    {"data": {"values": [{"x": 1}]},
     "layer": [
       {"mark": {"type": "rule", "strokeWidth": 2, "color": "var(--viz-s2)"}, "encoding": {"x": {"field": "x", "type": "quantitative"}}},
       {"mark": {"type": "text", "align": "left", "dx": 5, "y": -6, "text": "1× = no loss"}, "encoding": {"x": {"field": "x", "type": "quantitative"}}}
     ]}
  ]
}
Table view: how the ratios are computed

Simulation reference for LUMEN is the domain-randomised closed-loop row of thesis Table 6.2; hardware is run 2.

Item Hardware Simulation Ratio
LUMEN chamber pressure 0.7 % 0.6 % 1.2×
LUMEN coolant flow 1.1 % 0.5 % 2.2×
LUMEN mean of four outputs 1.3 % 0.5 % 2.6×
LUMEN injection temperature 0.8 % 0.3 % 2.7×
Cold-gas rig trajectory RMSE (Hörger et al. 2024, p. 9) 1.15 bar 0.36 bar 3.2×
LUMEN mixture ratio 2.7 % 0.5 % 5.4×

Where the gap comes from, according to the authors:

  • Actuator models. Twice the first hardware deployment failed on valve dynamics.
    • The thesis run 1 was "unstable due to a modeling error in the valve transfer function" (p. 149).
    • The EUCASS safety paper reports that the first test "induced oscillations … likely attributable to an inaccurate model of the valve dynamics" (Dauer et al. 2025, p. 7).
    • Domain randomisation of the plant did not cover this. The structure of the valve model was wrong, not just its parameters.
  • Plant model error larger than validation suggests.
    • On the calibration run, the EcosimPro model has 2.4 % MAPE on \(p_{cc}\) (Kurudzija et al. 2025, Table 2).
    • On the RL demonstration run the errors were 4.1 % mean on \(p_{cc}\), 4.9 % on coolant flow and up to 10.6 % maximum (thesis Table 6.3).
    • A possible cause the author gives: "for the first time the turbines are driven by methane instead of nitrogen".
  • Randomisation that does not contain reality. "Even with domain randomization, the controller seems to barely encounter the real-world characteristics during training" (p. 117). The randomisation ranges were ±1–10 % per parameter (Table A.3); the observed model errors reached 10.6 %.
  • Noise out of distribution. Real mixture-ratio noise was \(\sigma\) = 3.0 %, against a maximum of 1.5 % during training (p. 116).
  • Unexplained residual. "It is also not clear why small oscillations of about 0.5 Hz are still present" (p. 116).
{
  "$schema": "https://vega.github.io/schema/vega-lite/v6.json",
  "title": {"text": "Model error on the demonstration run vs the randomisation range", "subtitle": "Mean and maximum model error per output (thesis Table 6.3); vertical line: widest randomisation range (Table A.3)"},
  "width": "container", "height": 170,
  "layer": [
    {"data": {"values": [
        {"output": "Chamber pressure", "mean": 4.1, "max": 8.6},
        {"output": "Mixture ratio", "mean": 2.4, "max": 7.2},
        {"output": "Injection temperature", "mean": 3.9, "max": 7.7},
        {"output": "Coolant flow", "mean": 4.9, "max": 10.6}]},
     "encoding": {"y": {"field": "output", "type": "nominal", "sort": null, "title": null}},
     "layer": [
       {"mark": {"type": "rule", "strokeWidth": 2, "color": "var(--viz-axis)"},
        "encoding": {"x": {"field": "mean", "type": "quantitative", "title": "Model error (%)", "scale": {"domain": [0, 12]}}, "x2": {"field": "max"}}},
       {"transform": [{"fold": ["mean", "max"], "as": ["kind", "err"]},
                      {"calculate": "datum.kind === 'mean' ? 'Mean error' : 'Maximum error'", "as": "measure"}],
        "mark": {"type": "point", "filled": true, "size": 90, "stroke": "var(--md-default-bg-color)", "strokeWidth": 2},
        "encoding": {"x": {"field": "err", "type": "quantitative"},
          "color": {"field": "measure", "type": "nominal", "scale": {"domain": ["Mean error", "Maximum error"], "range": ["var(--viz-s1)", "var(--viz-s2)"]}, "legend": {"title": null}},
          "tooltip": [{"field": "output"}, {"field": "measure"}, {"field": "err", "title": "error (%)"}]}}
     ]},
    {"data": {"values": [{"x": 10}]},
     "layer": [
       {"mark": {"type": "rule", "strokeWidth": 2, "color": "var(--viz-ink-2)"}, "encoding": {"x": {"field": "x", "type": "quantitative"}}},
       {"mark": {"type": "text", "align": "right", "dx": -5, "y": -6, "text": "±10 %: widest randomisation"}, "encoding": {"x": {"field": "x", "type": "quantitative"}}}
     ]}
  ]
}
Table view: thesis Table 6.3, model errors on hot-fire run 2 (%)
\(p_{cc}\) \(R_{OF}\) \(T_{LNG}\) \(\dot m_{RC}\) TFV TOV FCV BPV
Mean 4.1 2.4 3.9 4.9 0.4 0.8 0.5 0.3
Max 8.6 7.2 7.7 10.6 2.2 4.3 4.3 1.6

The positive side, in the author's summary: control was successful "even in the presence of modeling errors of up to 10.6 %" and without fine-tuning (p. 118). The 1.3 % result is a zero-shot transfer. The fine-tuning dataset announced for the benchmark (RL4AA'25) is the obvious lever that DLR's own hardware controller did not use.

5.2 Safety: short tests, no guarantees

  • Closed-loop time on hardware is seconds.

    • The successful run was "over 16 s" (p. 117).
    • "Both tests were terminated prematurely due to different limiting factors" (Dauer et al. 2025, Fig. 4).
    • The run shown at the RL Bootcamp 2026 tracked for about 15 s before "a sensor failure" ended it (livestream).

    No published result shows an RL engine controller over a full-duration test or across many tests.

  • No stability or constraint guarantee.

    • The SAC controller satisfied all constraints in the simulated comparison, where MPC's soft constraints let coolant flow dip for 22 steps (p. 95).
    • That is an empirical result on one trajectory, not a guarantee.
    • The thesis outlook names "stability, robustness, and safety" as the open problem before flight use (pp. 123–126).
  • Faults outside the training distribution break the policy. In simulation, DLR cut the oxidiser-turbopump efficiency to 80 % at \(t\) = 27 s. The domain-randomised SAC agent was "unable to maintain the desired pressure level, as such a fault scenario was not included in the domain randomization" (Dauer et al. 2025, p. 10).
  • Knowing when not to trust the policy is at the first-step stage.
    • DLR's out-of-capability detector, like the PEDM baseline, rises immediately at that fault onset.
    • Its thresholds are the 99th percentile of training-data scores.
    • The paper reports this through plots and a single fault case. It gives no detection-rate or false-alarm statistics, and calls itself "a crucial first step" (Dauer et al. 2025).
  • Aggressive actuation.
    • The best simulated SAC controller used 60 % more valve motion than MPC (Δu 3.9 vs 2.4, Table 5.4).
    • It overdrove the turbine valves for about 1.1 s on large steps (p. 86).
    • The hardware controller showed ±2 % oscillations at 0.5 Hz (p. 113).
    • Valve oscillation is itself a hazard: fatigue, pressure waves, chugging (p. 60).
  • The safety system can end the episode for the wrong reason. Redline shutdowns fire on sensor readings, so a faulty sensor can abort a healthy test (DX'25 LUMEN page).

5.3 Partial observability

  • Unmeasured internal state.
    • Turbopump shaft torque is not measured.
    • Pump and turbine efficiencies are inferred indirectly.
    • The turbines were characterised on nitrogen, which has a speed of sound of about 350 m/s against about 500 m/s for hot methane (p. 67).
    • Wall and coolant thermal states are not observed at all.
  • Short memory against long time constants.

    • DLR's policies see the last 3 observations, 0.15 s of history at 20 Hz.
    • The plant has fuel-side settling times of 5.4–23.8 s (Table 4.7).

    My inference: a feed-forward policy cannot recover slow thermal state from 0.15 s of history. It must rely on the extra temperature and pressure channels DLR added to the observation (eq. 6.2). With only TFV/TOV and a user-chosen observation in the 2×2 challenge, that choice becomes the user's problem.

  • Delays.

    • Sensor filtering: the \(p_{cc}\) moving-average window was randomised over 0.05–0.15 s.
    • Valve dead time: 0.03–0.08 s (Table A.3).

    At 20 Hz these are 1–3 control steps.

  • Derived, noisy outputs. \(R_{OF}\) is a ratio of two flow-meter readings, so its noise (3.0 %) is ten times that of \(p_{cc}\) (0.3 %) (p. 116).

    {
      "$schema": "https://vega.github.io/schema/vega-lite/v6.json",
      "title": {"text": "What the policy remembers vs how slowly the plant moves", "subtitle": "Seconds, log scale. Thesis Table 4.7 (settling), Table A.3 (delays), p. 102 (3-step stacking at 20 Hz)"},
      "width": "container", "height": 190,
      "data": {"values": [
        {"item": "Valve dead time", "lo": 0.03, "hi": 0.08, "kind": "Plant and sensors"},
        {"item": "Sensor filter window, chamber pressure", "lo": 0.05, "hi": 0.15, "kind": "Plant and sensors"},
        {"item": "Policy history, 3 steps at 20 Hz", "lo": 0.15, "hi": 0.15, "kind": "What the policy sees"},
        {"item": "Settling after a TOV step", "lo": 0.4, "hi": 0.6, "kind": "Plant and sensors"},
        {"item": "Settling after a TFV step", "lo": 5.4, "hi": 23.8, "kind": "Plant and sensors"}
      ]},
      "encoding": {"y": {"field": "item", "type": "nominal", "sort": null, "title": null, "axis": {"labelLimit": 280}}},
      "layer": [
        {"mark": {"type": "rule", "strokeWidth": 4, "strokeCap": "round"},
         "encoding": {"x": {"field": "lo", "type": "quantitative", "scale": {"type": "log", "domain": [0.02, 40]}, "title": "Time (s, log scale)", "axis": {"values": [0.03, 0.1, 0.3, 1, 3, 10, 30]}}, "x2": {"field": "hi"},
           "color": {"field": "kind", "type": "nominal", "scale": {"domain": ["Plant and sensors", "What the policy sees"]}, "legend": {"title": null}}}},
        {"transform": [{"fold": ["lo", "hi"], "as": ["end", "t"]}],
         "mark": {"type": "point", "filled": true, "size": 70, "stroke": "var(--md-default-bg-color)", "strokeWidth": 2},
         "encoding": {"x": {"field": "t", "type": "quantitative"}, "color": {"field": "kind", "type": "nominal"},
           "tooltip": [{"field": "item"}, {"field": "lo", "title": "from (s)"}, {"field": "hi", "title": "to (s)"}]}}
      ]
    }

  • No preview of the reference.

    • Without future references in the observation, a policy can only react to a ramp. That is the lag visible in the bootcamp PPO demo, where the speaker attributed it to missing "future reference values" and valve delay (livestream).
    • With 4 steps of preview (D1 in §4) the thesis reached 0.3 % / 0.1 %.
    • For a vehicle whose thrust demand comes from a guidance loop, preview is unavailable; the thesis's hardware controller did without it (p. 102).
    • The challenge excludes preview too: its targets are generated in real time (organisers, Oct 2026). The ramp lag is part of the task, not a design choice.

5.4 Data: minutes of reality, days of simulation

17
ignitions of the whole engine, 2024–2025
> 20 min
accumulated engine hot-fire time
> 16 s
longest RL closed loop on the engine
≈ 1 M
simulator steps per day on 10 instances
≈ 5 days
to retrain the hardware controller
  • Real data is scarce.
    • LUMEN's two engine campaigns (2024, 2025) comprise 17 ignitions and "an accumulated hot-fire test duration of over 20 minutes" (Kurudzija et al. 2025, p. 4).
    • The turbopump campaigns add 88 min (oxidiser) and 44 min (fuel) of component runtime (same paper, p. 3).
    • Closed-loop RL hot fire on the whole engine totals well under a minute across the reported runs.
  • Simulation is slow.
    • The thesis trained at "about one million training steps per day" on 10 parallel EcosimPro instances (p. 83).
    • The hardware controller needed about 5 M steps and about 5 days to retrain (p. 118).
    • Domain randomisation doubled the training steps, from 1.5 M to 2.9 M (Table 5.3).
    • The challenge's simulator runs at about real time, and several instances can run in parallel (organisers, Oct 2026).
    • My extrapolation: at 20 Hz and real time, one simulator instance gives about 7 × 10⁴ steps per CPU hour. A laptop running 8 instances gets about 6 × 10⁵ steps an hour: enough for SAC-sized runs, but a 3 M-step PPO run takes most of a working day.
  • The benchmark data is not yet available.
    • The "dataset for fine-tuning" and the "simulated sensor and system errors" (RL4AA'25) have not been published. Nor has anything else (§7.1); a repository is expected around the end of October 2026 (organisers).
    • The fine-tuning data will not contain real hot-fire runs, which are export-controlled; the sim-to-real test cases change model parameters instead (same source). Real valve and sensor behaviour therefore stays out of reach for participants.
    • DLR's previous LUMEN benchmark, for DX'25 diagnosis, was only distributed on request (LiU page).
    • The underlying ESPSS library needs "prior approval from ESA" (brochure).

5.5 Comparability: there is no common scale yet

The results in §3 use at least six different metrics:

  • mean absolute percentage error;
  • integrated absolute error (IAE);
  • RMSE in bar;
  • summed episode reward;
  • settling time in a 2 % band;
  • success rate.

They also use at least five plants: a generic gas-generator model, three LUMEN model versions, the LUMEN engine, a cold-gas rig and a 22 N thruster. Only one DLR study (on the gas-generator model) reports a PID baseline, and only one reports MPC. For the challenge's own 2×2 task, no numbers of any kind are public. This is the gap the challenge's automatic evaluation is meant to close. Until it exists, cross-paper comparisons on this site are qualitative.

5.6 Limits of the benchmark as designed

These follow from the published design (AI4Aerospace 2025). They may change when the environment is released.

  • Two actuators only. With TFV and TOV as the only actions, coolant flow, injection temperature and the momentum-flux ratio are set by whatever fixed openings the other four valves have. The benchmark cannot test the multi-objective, constraint-boundary operation that D1 and D3 in §4 address.
  • Two faults. Test cases 6–7 use "two faults … simulated based on hot run data". Generalisation to unseen fault types is not tested.
  • No hardware in the loop. Public evaluation will be against simulators. The question that matters most, whether the controller works on the engine, stays with DLR.

5.7 Limits of this review

  • No numbers of my own on LUMEN. The challenge environment was not available. The only results of my own are on a surrogate engine written for this site (Baselines on the surrogate), which is calibrated to DLR's published numbers but says nothing quantitative about LUMEN or the challenge. Every LUMEN result here is reported by others.
  • Unread sources. Several DLR papers are DLR-internal or paywalled and were used at abstract level only (§7.11). The most important of these are:
    • the EUCASS 2025 model-validation paper, which I did read in full via eucass.eu;
    • the SciTech 2023 turbopump hardware paper, abstract only.
  • Speaker identity. The auto-captions name the bootcamp speaker "Yonas", while my brief named Kai Dresia. I describe the pitch by content, not by speaker.